Ac power, Fuses, Character set – Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual

Page 168: User memory

Advertising
background image

Specifications: 1400e Operator Terminal

C–7

Publication 2711E-821 – January 1998

Following are the ac power specifications for the PanelView 1400e
terminal.

Power Supply Type

Switching

Range

90–132, 180–264 V ac
automatic setting by the PanelView 1400e terminal to
match available power supply

Frequency Range

47–63 Hz

Power Consumption

Color terminal

75 W typical
100 W maximum

Volt Amps

Color terminal

180 VA typical
240 VA maximum

While the color terminal degausses, there is a 5.5-amp surge at
115 volts. At 230 V, there is an 11-amp surge that lasts less than
400 milliseconds. Automatic degauss occurs every time ac power is
re-applied to the terminal.

PanelView 1400e terminals:

Require one fuse for each ac line

Have fuses the user can access from the rear of the terminal

Accepts the following fuse type: BUSS GDC-3.15, 3.15 A,
250 V ac, 5 mm x 20 mm

!

ATTENTION: Fuses must be replaced by authorized
service personnel only. PanelView 1400e terminals
contain neutral fuses. Disconnect power before
servicing the unit.

PanelView 1400e terminals support the IBM character set for alarm,
local, and information messages.

PanelView 1400e terminals support:

256K bytes of Flash memory for application file

PCMCIA card slot of variable size (depends on user application
file)

RAM tests and Memory Checksum tests can be initiated in the
Terminal Diagnostics screen in Configuration mode.

AC Power

Fuses

Character Set

User Memory