Configuring PanelView Operator Terminals

Publication 2711E-821 – January 1998

To view application start-up settings:

"

Press the Application Startup button on the Terminal
Configuration screen to display the following screen.

Start-up Options Over RIO

By default, when an application is downloaded or made current and
the terminal is switched to Run mode, the first values written to the
PLC are the initial values. Also, after a power cycle, the initial value
or initial states values are written. When the terminal is switched
from Run to Configure to Run mode, the last state value is written.

If you choose No for Use Default Operation, the initial values or
state values are written when the terminal is in Run mode for the first
time. After a power cycle, or when switched between modes, the last
state value is written. When the terminal is switched from Run to
Configure to Run mode, the last state value is written. The default is
Yes for Use Default Operation.

When the terminal is switched from Run to Configure mode, nothing
is written.

Start-up Options Over DH+/ControlNet

By default, when an application is downloaded or made current and
the terminal is switched to Run mode, no initial values are written to
the PLC. As well, after a power cycle or when switching from
Configure to Run mode, no initial values are written. When the
terminal is switched from Run to Configure to Run mode, no initial
values are written.