Rockwell Automation 2711E-xxxx PanelView Operator Terminals User Manual User Manual

Page 44

Advertising
background image

2–13

Installing PanelView 1000e Terminals

Publication 2711E-821 – January 1998

Connecting a Terminal to Your PLC System

Figure 2.14 shows the Remote I/O and DH+

connector on the bottom

of the terminal. This connects the terminal to the host PLC over
Remote I/O or DH+.

Figure 2.14 Remote I/O and DH+ Connector

20163

1

On bottom of PanelView 1000e Terminal
(Refer to Figure 2.1)

Remote I/O and DH+ Plug
provided with installation kit

2

SHIELD

Remote I/O

PanelView Terminal

PLC

Shield

Shield

Pin1 Blue

Pin 1 Blue

Pin 2 Clear

Pin 2 Clear

DH+

PanelView Terminal

PLC

Shield

Shield

Pin1 Blue

Pin 2 Blue

Pin 2 Clear

Pin 1 Clear

To connect the PanelView 1000e terminal over Remote I/O:

1. Remove the Remote I/O and DH+ connector plug from the

bottom of the terminal. Figure 2.1 shows its location.

2. Back out plug terminal screws 2 and 1 on the connector. See

Figure 2.10 for plug connection locations.

3. Connect the clear wire to plug terminal 2 and the blue wire to

plug terminal 1. Connect shield and shield drain wire to middle
plug terminal. Tighten the screws to secure the wires.

4. Re-insert the plug into the terminal connector.

Note: If the terminal is the last device on the link, connect a 1/2 watt
terminating resistor across terminals 1 and 2. The value of the
resistor depends on the Remote I/O baud rate:

for 57.6 kilobaud and 115.2 kilobaud, use a 150-ohm resistor
(A-B Part Number 740018-29)

for 230 kilobaud, use an 82-ohm resistor (A-B Part Number
740018-23)

"

Advertising