HPR800XD Auto Gas –

806500

b-3

Pierce Complete

Input

When active, the system will use shield preflow gases during

piercing. When the signal is removed, the system will switch to shield

cutflow gases. The signal should be applied at the same time the

start signal is applied.

Corner Current

Input

When active, the system will switch to user specified corner current.

Remote Power

Input

Used to turn the power on or off

Not Ready for Start

Output

When on, this signal indicates that the plasma system is not ready for

a plasma start signal. This could be because the system is purging or

in test gas mode.

Ramp-down Error

Output

Indicates the arc did not ramp-down properly. Consumable life is

shortened.

TX+

Serial

Transmitting from the system

connect to cNc RX+

TX– Serial

Transmitting from the system

connect to cNc RX–

RX+ Serial

Receiving by the system

connect to cNc tX+

RX– Serial

Receiving by the system

connect to cNc tX–

Signal list (continued)

Signal name

type

Description

Hardware

Inputs – active low, dry contact, opto-isolated

Inactive: 24 V or open circuit, 0 mA

Active: 0 V or closed contact (0 ohm min, 6.5 mA; 200K ohm max, 0.1 mA)

Outputs – active low, open collector, opto-isolated

Inactive: Up to 40 V open circuit/open collector, 0 mA

Recommended 24 V pull-up into high impedance load

Active: 0.3 V max output into high impedance load, sinking capacitor up to 5 mA

Or 2k ohm minimum load resistance

Serial – RS422 serial communications