ILX34-AENWG ♦ Point I/O Platform

Ladder Logic

Wireless POINT I/O Adapter

User Manual

ProSoft Technology, Inc.

Page 117 of 177

August 16, 2013

5

Ladder Logic

In This Chapter

Adjusting the Input and Output Array Sizes (Optional) ........................ 117

1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference ..... 118

5.1

Adjusting the Input and Output Array Sizes (Optional)

The module internal database is divided into two user-configurable areas:
 Read Data
 Write Data.
The Read Data area is moved from the module to the processor, while the Write
Data area is moved from the processor to the module. You can configure the
start register and size of each area. The size of each area you configure must
match the Add-On instruction controller tag array sizes for the R

EAD

D

ATA

and

W

RITE

D

ATA

arrays.

The ILX34-AENWG sample program is configured for 600 registers of R

EAD

D

ATA

and 600 registers of W

RITE

D

ATA

,

which is sufficient for most application. This

topic describes how to configure user data for applications requiring more than
600 registers of ReadData and WriteData.

Important: Because the module pages data in blocks of 200 registers at a time, you must
configure your user data in multiples of 200 registers.

Caution: When you change the array size, RSLogix may reset the AENWG tag values to zero. To

avoid data loss, be sure to save your settings before continuing.

1 In the C

ONTROLLER

O

RGANIZATION

window, expand the D

ATA

T

YPES

and

U

SER

-D

EFINED

folders, and then double-click AENWGDATA.

This action

opens an edit window for the AENWGDATA data type.