ProSoft Technology ILX34-AENWG User Manual

Page 135

Advertising
background image

ILX34-AENWG ♦ Point I/O Platform

Ladder Logic

Wireless POINT I/O Adapter

User Manual

ProSoft Technology, Inc.

Page 135 of 177

August 16, 2013

Configuration Data

Data Type

Default Value

Valid Data Values

Program Value Channel 0

INT

0

-32,768…32,767

Low Engineering Channel 0

INT

0

-32,768…32,767

High Engineering Channel 0

INT

10,000

-32,768…32,767

Low Limit Channel 0

INT

-32,768

-32,768…32,767

High Limit Channel 0

INT

32,767

-32,768…32,767

Range Type Channel 0

SINT

1

1=0…10V
3=-10…+10V

Fault Mode Channel 0

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value

Idle Mode Channel 0

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value

Limit Alarm Latch Channel 0

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Fault Value Channel 1

INT

0

-32,768…32,767

Program Value Channel 1

INT

0

-32,768…32,767

Low Engineering Channel 1

INT

0

-32,768…32,767

High Engineering Channel 1

INT

10,000

-32,768…32,767

Low Limit Channel 1

INT

-32,768

-32,768…32,767

High Limit Channel 1

INT

32,767

-32,768…32,767

Range Type Channel 1

SINT

1

1=0…10V
3=-10…+10V

Fault Mode Channel 1

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value

Idle Mode Channel 1

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value

1734-OE2V

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-OE2V

2 Channel Analog Voltage Output