Configuration Data

Data Type

Default Value

Valid Data Values

Filter

SINT

120 (0x78H)

Filter_0

Filter_1

Filter_2

Filter_3

BIT 0
BIT 1
BIT 2
BIT 3

0000=No Filter
0001=50 kHz
0010=5 kHz
0100=500 Hz
1000=50 Hz

FilterA

FilterB

FilterZ

BIT 4
BIT 5
BIT 6

0=Input A/B/Z Not Filtered
1=Input A/B/Z Is Filtered

Decimal Position

SINT

0

Counter Config 0, 1, 2, 3, 4:
-128…+127 (0…255)
Counter Config 5, 6, & 7:
-4…+2

Time Base
(in 10 ms intervals)

INT

0

Counter Config 3 & 7 only:
0…3000 ms (10 ms…3 sec)

Gate Interval
(Product of Time Base x Gate Interval
must be

3000 ms)

SINT

0

Counter Config 3 & 7 only:
-128…+127 (0…200)

1734-VHSC24, 1734-VHSC5

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-VHSC24

1 Channel 15…24V dc Very High-speed Counter

1734-VHSC5

1 Channel 5V dc Very High-speed Counter

Configuration Data

Data Type

Default Value

Valid Data Values

Scalar

SINT

0

Counter Config 5, 6, 8 only:
-128…+127 (0…255) Single Bit only:
0, 1, 2, 4, 8, 16, 32, 64, -128

Output Ties 0

Out 0 Window 1

Out 0 Window 2

Out 0 Window 3

Out 0 Window 4

SINT
BIT 0
BIT 1
BIT 2
BIT 3

0


0=Output 0 Not Tied
1=Output 0 Tied to Window
Counter Config 3 (PWM):
Output 0 Window 1 PWM In

Output Ties 1

Out 1 Window 1

Out 1 Window 2

Out 1 Window 3

Out 1 Window 4

SINT
BIT 0
BIT 1
BIT 2
BIT 3

0


0=Output 1 Not Tied
1=Output 1 Tied to Window
Counter Config 3 (PWM):
Output 1 Window 1 PWM In

Rollover

DINT

16,777,215

1…16,777,216

Preset (< Rollover)

DINT

0

0…16,777,215

Advertising