About the Example Applications
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 54 of 177
ProSoft Technology, Inc.
August 16, 2013
b) Slot
In the M
ODULE
D
EFINITION
area of the dialog box, notice that the default
Connection type is R
ACK
O
PTIMIZATION
.
4 Click the C
ONNECTION
tab, and then change the RPI value for the module
from 20 (the default) to 10 (the recommended value for digital modules). This
value determines how often to exchange data with the ILX34-AENWG
adapter.
Important: To avoid overloading the ILX34-AENWG adapter, we recommend that RPI be no less
than 10 ms for rack connections and 50 ms for direct connections.
5 Click OK
save the configuration.