10 analog 2 channel input – ProSoft Technology ILX34-AENWG User Manual

Page 125

Advertising
background image

ILX34-AENWG ♦ Point I/O Platform

Ladder Logic

Wireless POINT I/O Adapter

User Manual

ProSoft Technology, Inc.

Page 125 of 177

August 16, 2013

5.2.10 Analog 2 Channel Input

1734-IE2C

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-IE2C

2 Channel Analog Current Input

Configuration Data

Data Type

Default Value

Valid Data Values

Low Engineering Channel 0

INT

3,277

-32,768…32,767

High Engineering Channel 0

INT

16,383

-32,768…32,767

Digital Filter Channel 0

INT

0

0…10,000 ms

Low Alarm Limit Channel 0

INT

3,113

-32,768…32,767

High Alarm Limit Channel 0

INT

16,547

-32,768…32,767

Low Low Alarm Limit Channel 0

INT

2,867

-32,768…32,767

High High Alarm Limit Channel 0

INT

16,793

-32,768…32,767

Range Type Channel 0

SINT

3

3=4…20 mA
8=0…20 mA

Limit Alarm Latch Channel 0

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Low Engineering Channel 1

INT

3,277

-32,768…32,767

High Engineering Channel 1

INT

16,383

-32,768…32,767

Digital Filter Channel 1

INT

0

0…10,000 ms

Low Alarm Limit Channel 1

INT

3,113

-32,768…32,767

High Alarm Limit Channel 1

INT

16,547

-32,768…32,767

Low Low Alarm Limit Channel 1

INT

2,867

-32,768…32,767

High High Alarm Limit Channel 1

INT

16,793

-32,768…32,767

Range Type Channel 1

SINT

3

3=4-20 mA
8=0-20 mA

Limit Alarm Latch Channel 1

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Notch Filter (Channel 0 & 1)

SINT

2

1=50 Hz
2=60 Hz
4=250 Hz
6=500 Hz

Real-time Sample (Channel 0 & 1)

INT

100

0…10,000 ms

1734-IE2C

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-IE2C

2 Channel Analog Current Input

Advertising