About the Example Applications

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 56 of 177

ProSoft Technology, Inc.

August 16, 2013

Note: If you receive an error message during these steps, refer to your RSLogix documentation to

interpret and correct the error.

3.4.4 Verify the Chassis Size

You must configure the chassis size for the ILX34-AENWG before you can make
any I/O Configure Chassis Size (page 39). The default setting for the chassis
size is 1 slot, which represents the adapter by itself.

When the adapter's non-volatile chassis size does not match the actual number
of modules present on its backplane, the adapter does not make any I/O
connections and an error occurs, as shown in the M

ODULE

P

ROPERTIES

dialog

box.

This procedure synchronizes the chassis size value from the RSLogix 5000
software into the ILX34-AENWG hardware. You must be online to perform this
procedure.

1 Verify that RSLogix 5000 software is online to the processor.
2 Double-click the ILX34-AENWG

adapter under I/O

C

ONFIGURATION

in the

C

ONTROLLER

O

RGANIZATION

window. This action opens the M

ODULE

P

ROPERTIES

dialog box.

3 On the M

ODULE

P

ROPERTIES

dialog box, click the C

ONNECTION

tab. Notice

that the M

ODULE

F

AULT

area of the dialog box contains information about the

error code.