ProSoft Technology ILX34-AENWG User Manual

Page 126

Advertising
background image

Ladder Logic

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 126 of 177

ProSoft Technology, Inc.

August 16, 2013

Input Data

Data Type

Default Value

Valid Data Values

Data Channel 0

INT

0

-32,768…32,767

Data Channel 1

INT

0

-32,768…32,767

Status Byte Channel 0

SINT

0

Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange

Status Byte Channel 1

SINT

0

Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange

Output Data

Data Type

Default Value

Valid Data Values

None

1734-IE2V

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-IE2V

2 Channel Analog Voltage Input

Configuration Data

Data Type

Default Value

Valid Data Values

Low Engineering Channel 0

INT

0

-32,768…32,767

High Engineering Channel 0

INT

10,000

-32,768…32,767

Digital Filter Channel 0

INT

0

0…10,000 ms

Low Alarm Limit Channel 0

INT

500

-32,768…32,767

High Alarm Limit Channel 0

INT

9,500

-32,768…32,767

Low Low Alarm Limit Channel 0

INT

200

-32,768…32,767

High High Alarm Limit Channel 0

INT

9,800

-32,768…32,767

Range Type Channel 0

SINT

2

0=-10…+10V
2=0…10V

Limit Alarm Latch Channel 0

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Low Engineering Channel 1

INT

0

-32,768…32,767

High Engineering Channel 1

INT

10,000

-32,768…32,767

Digital Filter Channel 1

INT

0

0…10,000 ms

Advertising