Ladder Logic

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 132 of 177

ProSoft Technology, Inc.

August 16, 2013

Configuration Data

Data Type

Default Value

Valid Data Values

Sensor Type Channel 1

SINT

5

0=mV
1=B
2=C
3=E
4=J
5=K
6=N
7=R
8=S
9=T

Digital Filter Channel 1

INT

0

0…10,000 ms

Low Alarm Limit Channel 1

INT

-32,768

-32,768…32,767

High Alarm Limit Channel 1

INT

32,767

-32,768…32,767

Low Low Alarm Limit Channel 1

INT

-32,768

-32,768…32,767

High High Alarm Limit Channel 1

INT

32,767

-32,768…32,767

1734-IT2

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-IT2

2 Channel Thermocouple Input, Isol.

Configuration Data

Data Type

Default Value

Valid Data Values

Temperature Mode Channel 1

SINT

1

0=mV/Custom Scale
1=°C
2=°F
3=°K
4=°R

Cold Junction Enable Channel 1

SINT

1

0=Disabled
1=Enabled

Cold Junction Offset Channel 1

INT

0

0…7,000 (0.00…70.00)

Input Data

Data Type

Default Value

Valid Data Values

Data Channel 0

INT

0

-32,768…32,767

Data Channel 1

INT

0

-32,768…32,767

Status Byte Channel 0

SINT

0

Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange