Ladder Logic

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 118 of 177

ProSoft Technology, Inc.

August 16, 2013

2 In the edit window, change the value of the R

EAD

D

ATA

array from INT[600] to

INT[1000] as shown, and then click A

PPLY

.

Note: If RSLogix resets your data values, refer to the backup copy of your program to re-enter your

configuration parameters.

3 Next, navigate to C

ONTROLLER

T

AGS

and double click to open an edit

window. Click the M

ONITOR

T

AGS

tab at the bottom of the edit window.

4 Click [+] to expand the AENWG.CONFIG.M

OD

D

EF

section, and then change

the R

EAD

R

EG

C

NT

parameter from 600 to 1000.

5 Save and download the sample program to the processor.
6 Go Online with the ControlLogix processor, and then toggle the

AENWG.CONTROL.W

ARM

B

OOT

bit to download the configuration to the

ILX34-AENWG module.

Note: Any changes made to the AENWG.CONFIG or WriteData arrays must be downloaded to the
ILX34-AENWG module. The use of the AENWG.CONTROL.WarmBoot or

AENWG.CONTROL.ColdBoot bit will cause the ILX34-AENWG module to re- read the

configuration from the ControlLogix processor.

To modify the W

RITE

D

ATA

array, follow the steps in this topic, but substitute

W

RITE

D

ATA

for ReadData throughout. Also, make sure that the R

EAD

D

ATA

and

W

RITE

D

ATA

arrays do not overlap in the module memory. For example, if your

application requires 2000 words of WriteData starting at register 0, then your
AENWG.CONFIG.M

OD

D

EF

.R

EAD

S

TART

R

EG

must be set to a value of 2000 or

greater.

5.2

1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference

Attention: You must use series C POINT I/O modules with the ILX34-AENWG adapter. Series A

or B POINT I/O modules will not work with this adapter.