11 specialty i/o – ProSoft Technology ILX34-AENWG User Manual

Page 136

Advertising
background image

Ladder Logic

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 136 of 177

ProSoft Technology, Inc.

August 16, 2013

Configuration Data

Data Type

Default Value

Valid Data Values

Limit Alarm Latch Channel 1

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Input Data

Data Type

Default Value

Valid Data Values

Status Byte Channel 0

SINT

0

Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm

Status Byte Channel 1

SINT

0

Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm

Output Data

Data Type

Default Value

Valid Data Values

Data Channel 0

INT

0

-32,768…32,767

Data Channel 1

INT

0

-32,768…32,767

5.2.11 Specialty I/O

1734-VHSC24, 1734-VHSC5

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-VHSC24

1 Channel 15…24V dc Very High-speed Counter

1734-VHSC5

1 Channel 5V dc Very High-speed Counter

Configuration Data

Data Type

Default Value

Valid Data Values

Counter Config

SINT

0

Config_0

Config_1

Config_2

Config_3

BIT 0
BIT 1
BIT 2
BIT 3

0000=0=Counter
0001=1=Encoder X1
0010=2=Encoder X2
0011=3=PWM
0100=4=Encoder X4
0101=5=Period/Rate
0110=6=Continuous/Rate
0111=7=Rate Measurement
1000=8=Pulse Generator

Mode_4

Mode_5

Mode_6

BIT 4
BIT 5
BIT 6

000=Store Count Disable
001=Store/Continue
010=Store/Wait/Resume
011=Store,Reset/Wait/Start
100=Store,Reset/Start

Z Input

BIT 7

0=Z Input Not Inverted
1=Z Input Is Inverted

Advertising