Ladder Logic

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 128 of 177

ProSoft Technology, Inc.

August 16, 2013

1734-IR2

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-IR2

2 Channel RTD Input

Configuration Data

Data Type

Default Value

Valid Data Values

Low Engineering Channel 0

INT

1,000

-32,768…32,767

High Engineering Channel 0

INT

5,000

-32,768…32,767

Digital Filter Channel 0

INT

0

0…10,000 ms

Low Alarm Limit Channel 0

INT

-32,768

-32,768…32,767

High Alarm Limit Channel 0

INT

32,767

-32,768…32,767

Low Low Alarm Limit Channel 0

INT

-32,768

-32,768…32,767

High High Alarm Limit Channel 0

INT

32,767

-32,768…32,767

Limit Alarm Latch Channel 0

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Sensor Type Channel 0

SINT

1

0=Ohms

2=200

Pt

385

5=100

JPt



3916

6=200

JPt

3916

9=10

Cu

427

10=120

Ni



672

11=100

Ni

618

12=120

Ni

618

Temperature Mode Channel 0

SINT

1

0=Custom Scale
1=°C
2=°F
3=°K
4=°R

Low Engineering Channel 1

INT

1,000

-32,768…32,767

High Engineering Channel 1

INT

5,000

-32,768…32,767

Digital Filter Channel 1

INT

0

0…10,000 ms

Low Alarm Limit Channel 1

INT

-32,768

-32,768…32,767

High Alarm Limit Channel 1

INT

32,767

-32,768…32,767

Low Low Alarm Limit Channel 1

INT

-32,768

-32,768…32,767

High High Alarm Limit Channel 1

INT

32,767

-32,768…32,767

Limit Alarm Latch Channel 1

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled
1=Alarms Disabled