ProSoft Technology ILX34-AENWG User Manual

Page 144

Advertising
background image

Ladder Logic

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 144 of 177

ProSoft Technology, Inc.

August 16, 2013

Error Bit

Description

6

A configuration was selected that requires the scalar and none was programmed OR
Multiple scalars were selected.

5

The preset is out of range (Rollover).

4

A rollover of zero was programmed through PWM was not selected OR
A rollover was programmed and PWM was selected OR
Rollover is out of range (>0x01000000).

3

A configuration requiring a time base was selected and no gate interval was set OR
Gate interval is out of range (>200) OR
Product of time base and gate interval is greater than 3 seconds.

2

A time base was entered that is not a multiple of 10 OR
Time base is out of range (>3000, or 3 seconds).

1

ZF/BF/AF were selected and no filter was programmed OR
Multiple filters were selected.

0

A reserved configuration/mode was programmed.

1734-IJ, 1734-IK

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-IJ

1 Channel 5V dc Encoder / Counter

1734-IK

1 Channel 15…24V dc Encoder / Counter

Output Data

Data Type

Default Value

Valid Data Values

Counter Control

SINT

0

Counter Reset

BIT 0

0

0=Count Unchanged
1=Count Cleared

Counter Preset

BIT 1

0

0=Count Unchanged
1=Count Set to Preset

Value Reset

(Stored / Accumulated Count)

BIT 2

0

0=Count Unchanged
1=Count Cleared

1734-SSI

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-SSI

1 Channel Synchronous Serial Interface

Configuration Data

Data Type

Default Value

Valid Data Values

Run

SINT

1

0=Module Not Running
1=Module Is Running

Gray Binary

SINT

1

0=Binary Code
1=Gray Code

Word Length

SINT

13

2…31