ProSoft Technology ILX34-AENWG User Manual

Page 134

Advertising
background image

Ladder Logic

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 134 of 177

ProSoft Technology, Inc.

August 16, 2013

Configuration Data

Data Type

Default Value

Valid Data Values

Low Limit Channel 1

INT

-32,768

-32,768…32,767

High Limit Channel 1

INT

32,767

-32,768…32,767

Range Type Channel 1

SINT

0

0=4…20 mA
2=0…20 mA

Fault Mode Channel 1

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value

1734-OE2C

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-OE2C

2 Channel Analog Current Output

Configuration Data

Data Type

Default Value

Valid Data Values

Idle Mode Channel 1

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value

Limit Alarm Latch Channel 1

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Input Data

Data Type

Default Value

Valid Data Values

Status Byte Channel 0

SINT

0

Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm

Status Byte Channel 1

SINT

0

Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm

Output Data

Data Type

Default Value

Valid Data Values

Data Channel 0

INT

0

-32,768…32,767

Data Channel 1

INT

0

-32,768…32,767

1734-OE2V

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-OE2V

2 Channel Analog Voltage Output

Configuration Data

Data Type

Default Value

Valid Data Values

Fault Value Channel 0

INT

0

-32,768…32,767

Advertising