ILX34-AENWG ♦ Point I/O Platform

Ladder Logic

Wireless POINT I/O Adapter

User Manual

ProSoft Technology, Inc.

Page 123 of 177

August 16, 2013

Output Data

Data Type

Default Value

Valid Data Values

Output Data - POINT 0, 1

SINT, BIT

0

0=Off
1=On

5.2.7 Digital 2 POINT Output - With Over Load Diagnostic Status

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-OV2E

2 POINT 10V…28V dc Electronically Fused Output, Sink

Configuration Data

Data Type

Default Value

Valid Data Values

Fault Mode - POINT 0, 1

SINT, BIT

0

0=Fault Value
1=Hold Last State

Fault Value - POINT 0, 1

SINT, BIT

0

0=Off
1=On

Program Mode - POINT 0, 1

SINT, BIT

0

0=Program Value
1=Hold Last State

Program Value - POINT 0, 1

SINT, BIT

0

0=Off
1=On

Auto Restart Enable - POINT 0, 1
(Over Load Behavior)

SINT, BIT

0

0=Latch Off
1=Auto Retry

Fault Latch Enable - POINT 0, 1
(Over Load)

SINT, BIT

0

0=No Latching
1=Alarms Latch

Input Data

Data Type

Default Value

Valid Data Values

Status Data - POINT 0, 1
(Over Load)

SINT, BIT

0

0=Off
1=On (Load Fault)

Output Data

Data Type

Default Value

Valid Data Values

Output Data - POINT 0, 1

SINT, BIT

0

0=Off
1=On

5.2.8 Digital 4 POINT Output - With Over Load and Open Load

Diagnostic Status

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-OB4E

4 POINT 10V…28V dc Electronically Fused Output, Source

Configuration Data

Data Type

Default Value

Valid Data Values

Fault Mode - POINT 0, 1, 2, 3

SINT, BIT

0

0=Fault Value
1=Hold Last State

Fault Value - POINT 0, 1, 2, 3

SINT, BIT

0

0=Off
1=On

Program Mode - POINT 0, 1, 2, 3

SINT, BIT

0

0=Program Value
1=Hold Last State