ProSoft Technology ILX34-AENWG User Manual

Page 42

Advertising
background image

Configure the ILX34-AENWG

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 42 of 177

ProSoft Technology, Inc.

August 16, 2013

o

0 = -10 to +10V dc

5 Click the value 2 and change it to 0, which changes the voltage range to -10

to +10V dc for channel 0.

Note the following:

o

The controller sends the configuration data only when it first establishes
the connection.

o

After you modify any of the tag values, you must download the updated
information into the module.

The best way to do this is to enter the correct code number in the Range
Type field when you add the I/O to the I/O Configuration tree. You then
download later.

If you need to change any of the module's configuration parameters after
adding the module, click the C

ONNECTION

tab and inhibit the module,

apply the changes, and then uninhibit the module. This action breaks the
connection and causes the configuration information to be downloaded
right after the connection is made.

Important: Switching the controller from Program to Run mode does not change the module

connection status and does not re-send module configuration data. We highly recommend that you

use the inhibit/uninhibit process and avoid power cycling.

6 Right-click the ILX34-AENWG adapter and select P

ROPERTIES

.

Advertising