ProSoft Technology ILX34-AENWG User Manual
Page 62

About the Example Applications
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 62 of 177
ProSoft Technology, Inc.
August 16, 2013
4 Click the C
ONNECTION
tab, and then change the RPI value for the module
from 20 (the default) to 50 (the recommended value for analog or specialty
modules). This value determines how often to exchange data with the ILX34-
AENWG adapter.
Important: To avoid overloading the ILX34-AENWG adapter, we recommend that RPI be no less
than 10 ms for rack connections and 50 ms for direct connections.
5 Click OK
save the configuration.
The following illustration shows the I/O Configuration for this project.
3.5.2 Add the Digital Output Module and Configure for Direct
Connection
1 Right-click the ILX34-AENWG adapter under the I/O Configuration folder and
select N
EW
M
ODULE
.