ProSoft Technology ILX34-AENWG User Manual

Page 26

Advertising
background image

Start Here

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 26 of 177

ProSoft Technology, Inc.

August 16, 2013

Be cautious about using DHCP software to configure your adapter. A DHCP
server typically assigns a finite lease time to the offered IP address.

When 50% of the leased time has expired, the ILX34-AENWG adapter attempts
to renew its IP address with the DHCP server.

The possibility exists that the adapter will be assigned a different IP address,
which would cause the adapter to cease communicating with the ControlLogix
controller.

Refer to Configure the ILX34-AENWG Adapter with Fixed IP Configure the
Adapter with Fixed IP Address (page 26).

Caution: To avoid unintended control, the ILX34-AENWG adapter must be assigned a fixed IP
address. The IP address of this adapter should not be dynamically provided. If a DHCP server is

used, it must be configured to assign a fixed IP address for your adapter.

Failure to observe this precaution may result in unintended machine motion or loss of process

control.

Configure the Adapter with Fixed IP Address

A fixed IP address prevents the adapter from losing a dynamically assigned IP
address and ceasing to communicate with the controller:

To configure the ILX34-AENWG adapter with a fixed IP address

1 Click the P

ORT

C

ONFIGURATION

tab in the ILX34-AENWG adapter properties

dialog.

2 Unselect (uncheck) the E

NABLE

DHCP

check box.

Advertising