Ladder Logic

ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 138 of 177

ProSoft Technology, Inc.

August 16, 2013

Configuration Data

Data Type

Default Value

Valid Data Values

On Value 1
Off Value 1
On Value 2
Off Value 2
On Value 3
Off Value 3
On Value 4
Off Value 4

DINT
DINT
DINT
DINT
DINT
DINT
DINT
DINT

0
0
0
0
0
0
0
0

Counter Config 3, 5, 6, 7:
0…16,777,215
Counter Config 0, 1, 2, 4:
0 to Rollover Value

SS PWM Value
(<0 or >9500 =Hold Last State)

INT

0

0…9500
(0.00…95.00%)

SS Counter Control

SINT

0

SS Counter Reset

BIT 0

0=Count Unchanged
1=Count Cleared

SS Counter Preset

BIT 1

0=Count Unchanged
1=Count Set to Preset

SS Value Reset

(Stored / Accum. Count)

BIT 2

0=Count Unchanged
1=Count Cleared

1734-VHSC24, 1734-VHSC5

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-VHSC24

1 Channel 15…24V dc Very High-speed Counter

1734-VHSC5

1 Channel 5V dc Very High-speed Counter

Configuration Data

Data Type

Default Value

Valid Data Values

SS Output Control

SINT

0

SS Out 0 Force

BIT 0

0=Output Off
1=Output Forced On

SS Out 0 En

BIT 1

0=Output Disabled
1=Output Enabled

SS Out 0 Electronic Fuse

BIT 2

0=Auto Retry
1=Latch Off

SS Out 0 Diagnostic Speed

BIT 3

0 ≤ 8 ms Response
1=50 ms Response

SS Out 1 Force

BIT 4

0=Output Off
1=Output Forced On

SS Out 1 En

BIT 5

0=Output Disabled
1=Output Enabled

SS Out 1 Electronic Fuse

BIT 6

0=Auto Retry
1=Latch Off

SS Out 1 Diagnostic Speed

BIT 7

0 ≤ 8 ms Response
1=50 ms Response

To enter values from +128 to +255, use these conversion formulas:
 Desired Decimal Position Value - 256 = Entered Decimal Position Value.

Example: for a divisor of 200, 200 - 256 = -56