When the adapter's non-volatile chassis size does not match the actual number
of modules present on its backplane, the adapter does not make any I/O
connections and an error occurs, as shown in the M
ODULE
P
ROPERTIES
dialog
box.
This procedure synchronizes the chassis size value from the RSLogix 5000
software into the ILX34-AENWG hardware. You must be online to perform this
procedure.
1 Verify that RSLogix 5000 software is online to the processor.
2 Double-click the ILX34-AENWG
adapter under I/O
C
ONFIGURATION
in the
C
ONTROLLER
O
RGANIZATION
window. This action opens the M
ODULE
P
ROPERTIES
dialog box.
3 On the M
ODULE
P
ROPERTIES
dialog box, click the C
ONNECTION
tab. Notice
that the M
ODULE
F
AULT
area of the dialog box contains information about the
error code.