Example: for a 40,000 count sensor, 40000 - 65536 = -25536

Sensor Cycle
To enter Cycle values from +32,768 to +65,535, use this conversion formula:
 Desired Cycle Value - 65536 = Entered Cycle Value.

Example: for 50,000 sensor cycle rotations, 50000 - 65536 = -15536
Compare 0,1 Value

To enter Compare values from +2,147,483,647 to +4,294,967,295, use this
conversion formula:
 Desired Compare Value - 4,294,967,296 = Entered Compare Value.

Example: for a 3,000,000,000 compare value,
3,000,000,000 - 4,294,967,296 = -1,294,967,296

1734-SSI

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-SSI

1 Channel Synchronous Serial Interface

Input Data

Data Type

Default Value

Valid Data Values

Present Data

DINT

0

-2,147,483,648…2,147,483,647
(0…4,294,967,295)

Latched Data

DINT

0

-2,147,483,648…2,147,483,647
(0…4,294,967,295)

Status

INT

0

Input Status

BIT 0

0=Input is Off
1=Input is On

Run

BIT 1

0=Module is not Running
1=Module is Running

Decreasing Count

BIT 2

0=Count not Decreasing
1=Count is Decreasing

Increasing Count

BIT 3

0=Count not Increasing
1=Count is Increasing

Compare0 Reached
Compare1 Reached

BIT 4
BIT 5

0=Compare not Reached
1=Compare was Reached

Compare0 Status
Compare1 Status

BIT 6
BIT 7

0=Compare Off
1=Compare On

Power Fault

BIT 8

0=No 24Vdc Power Fault
1=24Vdc Power Fault

Configuration Fault

BIT 9

0=No FPGA Config Fault
1=FPGA Config data bad

Communication Fault

BIT 10

0=No FPGA Comm Fault
1=FPGA Comm Fault

Input Data Fault

BIT 11

0=No Input Data Fault
1=Input Power Fault (short)

Data Latched

BIT 12

0=Input Data Not Latched
1=Input Data Latched

Advertising