About the Example Applications
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 50 of 177
ProSoft Technology, Inc.
August 16, 2013
I/O modules set up to use rack optimization communicate at the rate of the
RPI configured for the ILX34-AENWG adapter.
I/O modules configured for direct communication communicate at their own
set RPI and ignore the ILX34-AENWG adapter RPI.
Attention: You must use series C POINT I/O modules with the ILX34-AENWG adapter. Series A
or B POINT I/O modules will not work with this adapter.
3.4.1 Add the Relay Output Module and Configure for Direct
Connection
1 Right-click the ILX34-AENWG adapter under the I/O Configuration folder and
select N
EW
M
ODULE
.
2 In the S
ELECT
M
ODULE
dialog box, choose the 1734-OW2 relay output
module from the list, and click OK.
3 In the
M
ODULE
P
ROPERTIES
dialog, enter the following information:
a) Name