ProSoft Technology ILX34-AENWG User Manual

Page 149

Advertising
background image

ILX34-AENWG ♦ Point I/O Platform

Ladder Logic

Wireless POINT I/O Adapter

User Manual

ProSoft Technology, Inc.

Page 149 of 177

August 16, 2013

Configuration Data

Data Type

Default Value

Valid Data Values

DeviceNet Record Header Mode

SINT

0

0=Transmit Handshake
1=Transmit Immediate

Transmit Data / Receive Data / Delimiter / Pad Character

Note: 7 data bits allows ASCII Character data values of 0 to 127, which RSLogix 5000 software

does support in the signed Short Integer data type SINT (-128 to +127 range).

Note that 8 data bits allows ASCII Character data values of 0 to 255.

To enter values from +128 to +255, use this conversion formula:
Desired Decimal Value - 256 = Entered Decimal Value.

Example: for an ASCII Character value of 128,

128 - 256 = -128

1734-232ASC

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-232ASC

1 Channel ASCII Interface Module

Input Data

Data Type

Default Value

Valid Data Values

Receive Record Number

SINT

0

-128…+127 (0…255)

Status

SINT

0

TX FIFO Overflow

BIT 0

0=No Error
1=TX FIFO Overflow Error

RX FIFO Overflow

BIT 1

0=No Error
1=RX FIFO Overflow Error

RX Parity Error

BIT 2

0=No Error
1=RX Parity Overflow Error

Handshake Error

BIT 6

0=No Error
1=Handshake Error

New Data Flag

BIT 7

0=No New Data
1=New Data Present

Length_Lo

SINT

20

-128…+127 (0…128)

Length_Hi

SINT

0

0 or 1

Data[128]

SINT

0

Received ASCII Message

Output Data

Data Type

Default Value

Valid Data Values

Transmit Record Number

SINT

0

-128…+127 (0…255)

Receive Record Number

SINT

0

-128…+127 (0…255)

Status

SINT

0

TX FIFO Overflow

BIT 0

0=No Error
1=TX FIFO Overflow Error

RX FIFO Overflow

BIT 1

0=No Error
1=RX FIFO Overflow Error

Advertising