ILX34-AENWG ♦ Point I/O Platform

Ladder Logic

Wireless POINT I/O Adapter

User Manual

ProSoft Technology, Inc.

Page 133 of 177

August 16, 2013

Input Data

Data Type

Default Value

Valid Data Values

Status Byte Channel 1

SINT

0

Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange

Cold Junction Data

INT

0

-32,768…32,767

Output Data

Data Type

Default Value

Valid Data Values

None

1734-OE2C

1734 POINT I/O Catalog Number

RSLogix5000 Module Description

1734-OE2C

2 Channel Analog Current Output

Configuration Data

Data Type

Default Value

Valid Data Values

Fault Value Channel 0

INT

0

-32,768…32,767

Program Value Channel 0

INT

0

-32,768…32,767

Low Engineering Channel 0

INT

1,638

-32,768…32,767

High Engineering Channel 0

INT

8,191

-32,768…32,767

Low Limit Channel 0

INT

-32,768

-32,768…32,767

High Limit Channel 0

INT

32,767

-32,768…32,767

Range Type Channel 0

SINT

0

0=4…20 mA
2=0…20 mA

Fault Mode Channel 0

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value

Idle Mode Channel 0

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value

Limit Alarm Latch Channel 0

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Fault Value Channel 1

INT

0

-32,768…32,767

Program Value Channel 1

INT

0

-32,768…32,767

Low Engineering Channel 1

INT

1,638

-32,768…32,767

High Engineering Channel 1

INT

8,191

-32,768…32,767