Frequency-related Functions

Frequency Limits – Upper and lower
limits can be imposed on the inverter
output frequency. These limits will apply
regardless of the source of the speed refer-
ence. You can configure the lower
frequency limit to be greater than zero as
shown in the graph. The upper limit must
not exceed the rating of the motor or
capability of the machinery. The
maximum frequency setting (A004/A204)
takes precedence over frequency upper
limit (A061/A261).

Upper

limit

Frequency command

Lower

limit

Settable

range

Output

frequency

0

A061

A062

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

A061 Frequency upper limit

setting

Sets a limit on output
frequency less than the
maximum frequency (A004).
Range is from frequency lower
limit (A062) to maximum
frequency (A004).
0.0.. setting is disabled
>0.1 setting is enabled

✘ ✔

0.0

0.0

Hz

Lim H 0000.0Hz

A261 Frequency upper limit

setting, 2nd motor

Sets a limit on output
frequency less than the
maximum frequency (A004).
Range is from frequency lower
limit (A262) to maximum
frequency (A204).
0.0.. setting is disabled
>0.1 setting is enabled

✘ ✔

0.0

0.0

Hz

2Lim H 0000.0Hz

A062 Frequency lower limit

setting

Sets a limit on output
frequency greater than zero.
Range is start frequency
(B082) to frequency upper
limit (A061).
0.0.. setting is disabled
>0.1 setting is enabled

✘ ✔

0.0

0.0

Hz

Lim L 0000.0Hz

A262 Frequency lower limit

setting, 2nd motor

Sets a limit on output
frequency greater than zero.
Range is start frequency
(B082) to frequency upper
limit (A261).
0.0.. setting is disabled
>0.1 setting is enabled

✘ ✔

0.0

0.0

Hz

2Lim L 0000.0Hz