Appendix B

B–19

ModBus Data Listing

ModBus Coil List

The following tables list the primary coils for the inverter interface to the network. The
table legend is given below.

Coil Number - The network register address offset for the coil, in hex and decimal.

Actual network address is 30001 + offset. The coil data is a single bit (binary) value.

Name - The functional name of the coil

R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data

Description - The meaning of each of the states of the coils

List of Coil Numbers

Coil Number

Name

R/W

Description

hex

dec.

0000h

00000 (Reserved)

R

0001h

00001 Run command

R/W

0 .... Stop
1 .... Run (enabled when A003=03)

0002h

00002 FW/REV command

R/W

0 .... REV
1 .... FW (enabled when A003=03)

0003h

00003 External trip (EXT)

R/W

0 .... No trip event
1 .... Trip occurred

0004h

00004 Trip reset (RS)

R/W

0 .... No reset condition
1 .... Reset

0005h

00005 (Reserved)

R

0006h

00006 (Reserved)

R

0007h

00007 Intelligent input terminal 1

R/W

0 .... OFF *1
1 .... ON

0008h

00008 Intelligent input terminal 2

R/W

0009h

00009 Intelligent input terminal 3

R/W

000Ah 00010 Intelligent input terminal 4

R/W

000Bh 00011 Intelligent input terminal 5

R/W

000Dh 00013 (Not used)

000Eh

00014 Run/Stop status

R

0 .... Stop (corresponds to D003
monitor)
1 .... Run

000Fh

00015 FW/REV status

R

0 .... FW
1 .... RV

0010h

00016 Inverter ready

R

0 .... Not ready
1 .... Ready

0011h

00017 (Reserved)

R

0012h

00018 (Reserved)

R