ModBus Data Listing

Appendix B

B–40

C041

Overload level setting

R/W Sets the overload signal level

between 0% and 200% (from
0 to two times the rated
current of the inverter)

1124h

04388

0 to

20000

0.01 %

C042

Frequency arrival
setting for acceleration

R/W Sets the frequency arrival

setting threshold for the
output frequency during
acceleration, range is 0.0 to
400.0 Hz

1126h

04390 0 to 4000

*1

0.1 Hz

C043

Arrival frequency
setting for deceleration

R/W Sets the frequency arrival

setting threshold for the
output frequency during
deceleration, range is 0.0 to
400.0 Hz

1128h

04392 0 to 4000

0.1 Hz

C044

PID deviation level
setting

R/W Sets the allowable PID loop

error magnitude (absolute
value), SP - PV, range is 0.0 to
100%, resolution is 0.1%

1129h

04393 0 to 1000

0.1 %

C052

PID FBV function high
limit

R/W When the PV exceeds this

value, the PID loop turns OFF
the PID Second Stage Output,
range is 0.0 to 100.0%

112Eh

04398 0 to 1000

0.1 %

C053

PID FBV function low
limit

R/W When the PV goes below this

value, the PID loop turns ON
the PID Second Stage Output,
range is 0.0 to 100.0%

112Fh

04399 0 to 1000

0.1 %

C071

Communication speed
selection

NOTE: These network

settings are not accessible to

ModBus. Use the inverter

keypad or digital operator to

edit. Refer to

“Network

Communication Settings”

on page 3–58

.

1138h

04408

C072

Node allocation

1139h

04409

C074

Communication parity
selection

113Bh 04411

C075

Communication stop bit
selection

113Ch 04412

C076

Communication error
select

113Dh 04413

C077

Communication error
time-out

113Eh

04414

C078

Communication wait
time

113Fh

04415

“C” Group Intelligent Terminal Functions

Func.

Code

Name

R/W

Description

Network Data

Register

Range

Res.

hex

dec.