“B” Group: Fine Tuning Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–46

B150: Carrier Mode – If B083 Carrier Frequency setting is greater than 4 kHz, then
the B150 Carrier Mode function (if enabled) will reduce the actual carrier frequency
downward to 4 kHz as the inverter’s internal termperature increases.

B151: Quick start enable – This function and the intelligent input [RDY] (option code
52) have the same effect. If you need the inverter output to always have a quick response,
use parameter B151 and do not assign the [RDY] input. Otherwise, disable Quick Start
Enable (set B151=00) and assign the [RDY] input. Then you can enable the Quick Start
feature only when necessary. When the Quick Start feature is enabled, then access to
parameter editing is the same as when the inverter is in Run Mode.

NOTE: Parameter B151 cannot be read and copied to another inverter. This prevents
turning ON another inverter’s output unexpectedly.

B131 Over-voltage

LADSTOP level

Sets the threshold level for
over-voltage LADSTOP. When
the DC bus voltage is above the
threshold value, the inverter
stops deceleration until the DC
bus voltage is less than the
threshold setting again.
Two voltage ranges with 1V
resolution:
200V class: 330 to 390V
400V class: 660 to 780V

✔ ✔

380 /

760

380 /

760

V

LADST LVL 00380V

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

B150 Carrier mode

Automatically reduces the
actual carrier frequency as
needed to avoid internal
overheating. Two option codes:
00... Disable
01... Enable

✘ ✔

00

00

Cr-DEC OFF

B151 Quick start enable

Enables inverter output for
constant ON operation to speed
up response. Two option codes:
00... Disable
01... Enable

✔ ✔

00

00

RDY-Func OFF