B–37, Appendix b – Hitachi L2002 User Manual

Page 273

Advertising
background image

L200

2

Inverter

Appendix B

B–37

B089

Monitor display select
for networked inverter

R/W Selects the parameter

displayed on the keypad
display when the inverter is
networked, 7 options:
01... Output frequency
monitor
02... Output current monitor
03... Rotation direction
monitor
04... Process variable (PV),
PID feedback monitor
05... Intelligent input terminal
status
06... Intelligent output
terminal status
07... Scaled output frequency
monitor

10D8h 04312

1 to 7

B091

Stop mode selection

R/W Selects how the inverter stops

the motor, two option codes:
00... DEC (decelerate and
stop)
01... FRS (free run to stop)

10DA

h

04314

0, 1

B130

Over-voltage
LADSTOP enable

R/W Pauses deceleration ramp

when DC bus voltage rises
above threshold level, in order
to avoid over-voltage trip.
Two option codes:
00... Disable
01... Enable

10F5h

04341

0, 1

B131

Over-voltage
LADSTOP level

R/W Sets the threshold level for

over-voltage LADSTOP.
When the DC bus voltage is
above the threshold value, the
inverter stops deceleration
until the DC bus voltage is
less than the threshold setting
again.

10F6h

04342

330 to

390,

660 to

780

1 V

B150

Carrier mode (not
accessible to ModBus)

Automatically reduces the
carrier frequency as the
ambient temperature
increases.
Two option codes:
00... Disable
01... Enable

10F8h

04344

0, 1

“B” Group Fine Tuning Functions

Func.

Code

Name

R/W

Description

Network Data

Register

Range

Res.

hex

dec.