Unattended Start Protection

If the Run command is already set when power is turned ON, the inverter starts running
immediately after powerup. The Unattended Start Protection (USP) function prevents
that automatic startup, so that the inverter will not run without outside intervention.
When USP is active and you need to reset an alarm and resume running, either turn the
Run command OFF, or perform a reset operation by the terminal [RS] input or the
keypad Stop/reset key.

In the figure below, the [UPS] feature is enabled. When the inverter power turns ON, the
motor does not start, even though the Run command is already active. Instead, it enters
the USP trip state, and displays E13 error code. This requires outside intervention to
reset the alarm by turning OFF the Run command per this example (or applying a reset).
Then the Run command can turn ON again and start the inverter output.

Inverter output frequency

Inverter power supply

[USP] terminal

Alarm output terminal

RUN command [FW, RV]

Run

command

Alarm

cleared

Alarm

display

E13

t

1
0
1
0
1
0
1
0
1
0

Events:

Option

Code

Terminal

Symbol

Function Name

Input

State

Description

13

USP

Unattended Start
Protection

ON

On powerup, the inverter will not resume a Run
command (mostly used in the US)

OFF

On powerup, the inverter will resume a Run
command that was active before power loss

Valid for inputs:

C001, C002, C003, C004,
C005

Required settings:

(none)

Notes:

Note that when a USP error occurs and it is
canceled by a reset from a [RS] terminal input, the
inverter restarts running immediately.

Even when the trip state is canceled by turning the
terminal [RS] ON and OFF after an under voltage
protection E09 occurs, the USP function will be
performed.

When the running command is active immediately
after the power is turned ON, a USP error will
occur. When this function is used, wait for at least
three (3) seconds after the powerup to generate a
Run command.

Example (default input configuration shown for
–FU models; –FE and –FR models require input
configuration—see page

3–47

):

See I/O specs on page

4–6

.

USP