“A” Group: Standard Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–30

Analog Input Calculate Function – The inverter can mathematically combine two
input sources into one value. The Calculate function can either add, subtract, or multiply
the two selected sources. This provides the flexibility needed by various applica-
tions.You can use the result for the output frequency setting (use A001=10) or for the
PID Process Variable (PV) input (use A075=03).

A141

[O] input

Potentiometer

[OI] input

Network variable F001

Digital operator

[O] input

Potentiometer

[OI] input

Network variable F001

Digital operator

A142

A input

select

A143

• 00 A + B
• 01 A – B
• 02 A x B

A
B

“CAL”

(result)

B input

select

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

A141 A input select for

calculate function

Five options:
00... Digital operator
01... Keypad potentiometer
02... [O] input
03... [OI] input
04... Network variable

✘ ✔

02

02

CALC Slct1 O

A142 B input select for

calculate function

Five options:
00... Digital operator
01... Keypad potentiometer
02... [O] input
03... [OI] input
04... Network variable

✘ ✔

03

03

CALC Slct2 OI

A143 Calculation symbol

Calculates a value based on the
A input source (A141 selects)
and the B input source (A142
selects). Three options:
00... ADD (A input + B input)
01... SUB (A input – B input)
02... MUL (A input x B input)

✘ ✔

00

00

CALC SMBL ADD