B–35, Appendix b – Hitachi L2002 User Manual

Page 271

Advertising
background image

L200

2

Inverter

Appendix B

B–35

B021

Overload restriction
operation mode

R/W Select the operating mode

during overload conditions,
three options, option codes:
00... Disabled
01... Enabled for acceleration
and constant speed
02... Enabled for constant
speed only

10B5h 04277

0, 1, 2

B022

Overload restriction
setting

R/W Sets the level for overload

restriction, between 20% and
150% of the rated current of
the inverter, setting resolution
is 1% of rated current

10B6h 04278

2000 to

15000

0.01%

B023

Deceleration rate at
overload restriction

R/W Sets the deceleration rate

when inverter detects
overload, range is 0.1 to 30.0,
resolution is 0.1

10B7h 04279

1 to 300

0.1 sec

B028

Overload restriction
source selection

R/W Two options; select codes:

00... B022/B222 setting level
01... [O]–[L] analog input

10BBh 04283

0, 1

B228

Overload restriction
source selection, 2nd
motor

R/W Two options; select codes:

00... B022/B222 setting level
01... [O]–[L] analog input

152Bh 05419

0, 1

B031

Software lock mode
selection

R/W Prevents parameter changes,

in four options, option codes:
00... all parameters except
B031 are locked when [SFT]
terminal is ON
01... all parameters except
B031 and output frequency
F001 when [SFT] terminal is
ON
02... all parameters except
B031 are locked
03... all parameters except
B031 and output frequency
F001 setting are locked

10BCh 04284 0, 1, 2, 3

B080

[AM] analog signal
gain

R/W Adjust of analog output at

terminal [AM],
range is 0 to 255

10CFh 04303

0 to 255

B082

Start frequency adjust-
ment

R/W Sets the starting frequency for

the inverter output, range is
0.5 to 9.9 Hz

10D1h 04305

5 to 99

0.1 Hz

“B” Group Fine Tuning Functions

Func.

Code

Name

R/W

Description

Network Data

Register

Range

Res.

hex

dec.

Advertising