Frequency Arrival Signals

The Frequency Arrival group of outputs help coordinate external systems with the
current velocity profile of the inverter. As the name implies, output [FA1] turns ON
when the output frequency arrives at the standard set frequency (parameter F001).
Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility.
For example, you can have an output turn ON at one frequency during acceleration, and
have it turn OFF at a different frequency during deceleration. All transitions have hyster-
esis to avoid output chatter if the output frequency is near one of the thresholds.

Option

Code

Terminal

Symbol

Function Name

Output

State

Description

01

FA1

Frequency Arrival
Type 1 – Constant
Speed

ON

when output to motor is at the set frequency

OFF

when output to motor is OFF, or in any accelera-
tion or deceleration ramp

02

FA2

Frequency Arrival
Type 2 – Over-
frequency

ON

when output to motor is at or above the FA2
threshold (C042) during accel

OFF

when output to motor is below the FA2 threshold
(C043) during decel

Valid for outputs:

11, 12, AL0 – AL2

Required settings:

(none)

Notes:

For most applications you will need to use only one
type of frequency arrival outputs (see examples).
However, it is possible assign both output terminals
to output functions [FA1] and [FA2].

For each frequency arrival threshold, the output
anticipates the threshold (turns ON early) by 1.5Hz.

The output turns OFF as the output frequency
moves away from the threshold, delayed by 0.5Hz.

The delay time of the output signal is 60 ms
(nominal).

The example circuit for terminal [12] drives a relay
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from
damaging the inverter’s output transistor.

Example (default output configuration
shown—see page

3–54

):

Inverter output
terminal circuit

RY

+

FA1

Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
see pages

4–36

and

3–54

):

AL0

AL2

AL1

Inverter logic
circuit board

See I/O specs
on page

4–6

.

FA1

Load

Power

supply

12 11

CM2