The following table lists the holding registers for the “C” Group Intelligent Input
Functions.

I

“C” Group Intelligent Terminal Functions

Func.

Code

Name

R/W

Description

Network Data

Register

Range

Res.

hex

dec.

C001

Terminal [1] function

R/W

See

“Input Terminal

Configuration” on page 3–

47

1103h

04355 0, 1, 2, 3,

4, 5, 6, 7,

8, 9, 11,

12, 13,
15, 16,
18, 19,
20, 21,
22, 23,
24, 27,
28, 29,
31, 50,

51, 255

C002

Terminal [2] function

R/W

1104h

04356

C003

Terminal [3] function

R/W

1105h

04357

C004

Terminal [4] function

R/W

1106h

04358

C005

Terminal [5] function

R/W

1107h

04359

C011

Terminal [1] active state R/W Select logic convention, two

option codes:
00... normally open [NO]
01... normally closed [NC]

110Bh 04363

0, 1

C012

Terminal [2] active state R/W

110Ch 04364

0, 1

C013

Terminal [3] active state R/W

110Dh 04365

0, 1

C014

Terminal [4] active state R/W

110Eh

04366

0, 1

C015

Terminal [5] active state R/W

110Fh

04367

0, 1

C021

Terminal [11] function

R/W

See

“Output Terminal

Configuration” on page 3–

54

1114h

04372

0, 1, 2, 3,
4, 5, 6, 7,

8, 9

C022

Terminal [12] function

R/W

1115h

04373

C026

Alarm relay terminal
function

R/W

1119h

04377

C028

[AM] signal selection

R/W Two available functions:

00... Actual motor speed
01... Motor current

111Bh 04379

0, 1

C031

Terminal [11] active
state

R/W Select logic convention, two

option codes:
00... normally open (NO)
01... normally closed (NC)

111Dh 04381

0, 1

C032

Terminal [12] active
state

R/W Select logic convention, two

option codes:
00... normally open (NO)
01... normally closed (NC)

111Eh

04382

0, 1

C036

Alarm relay active state

R/W Select logic convention, two

option codes:
00... normally open (NO)
01... normally closed (NC)

1122h

04370