Additional Analog Input Settings

Input Range Settings – The parameters in the following table adjust the input charac-
teristics of the analog current input. When using the inputs to command the inverter
output frequency, these parameters adjust the starting and ending ranges for the current,
as well as the output frequency range. Related characteristic diagrams are located in

“Analog Input Settings” on page 3–14

.

“A” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

A101 [OI]–[L] input active

range start frequency

The output frequency corre-
sponding to the current input
range starting point.
Range is 0.00 to 400.0 Hz

✘ ✔

0.0

0.0

Hz

OI-EXS 0000.0Hz

A102 [OI]–[L] input active

range end frequency

The output frequency corre-
sponding to the current input
range ending point.
Range is 0.00 to 400.0 Hz

✘ ✔

0.0

0.0

Hz

OI-EXE 0000.0Hz

A103 [OI]–[L] input active

range start current

The starting point for the
current input range.
Range is 0. to 100.%

✘ ✔

0.0

0.0

%

OI-EX%S 00000%

A104 [OI]–[L] input active

range end current

The ending point for the
current input range.
Range is 0. to 100.%

✘ ✔

100.

100.

%

OI-EX%E 00100%

A105 [OI]–[L] input start

frequency enable

Two options:
00 .. Use A101 start value
01 .. Use 0Hz

✘ ✔

01

01

OI-LVL 0Hz