B–34, Appendix b – Hitachi L2002 User Manual

Page 270

Advertising
background image

ModBus Data Listing

Appendix B

B–34

The following table lists the holding registers for the “B” Group Fine Tuning Functions.

“B” Group Fine Tuning Functions

Func.

Code

Name

R/W

Description

Network Data

Register

Range

Res.

hex

dec.

B001

Selection of automatic
restart mode

R/W Select inverter restart method,

four option codes:
00... Alarm output after trip,
no automatic restart
01... Restart at 0Hz
02... Resume operation after
frequency matching
03... Resume previous freq.
after freq. matching, then
decelerate to stop and display
trip info.

10A5h 04261 0, 1, 2, 3

B002

Allowable under-
voltage power failure
time

R/W The amount of time a power

input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the
restart mode is selected.

10A6h 04262

3 to 250

0.1 sec

B003

Retry wait time before
motor restart

R/W Time delay after under-

voltage condition goes away,
before the inverter runs motor
again.
Range is 0.3 to 100 seconds.

10A7h 04263

3 to

1000

0.1 sec

B004

Instantaneous power
failure / under-voltage
trip alarm enable

R/W Two option codes:

00... Disable
01... Enable

10A8h 04264

0, 1

B005

Number of restarts on
power failure / under-
voltage trip events

R/W Two option codes:

00... Restart 16 times
01... Always restart

10A9h 04265

0, 1

B012

Level of electronic
thermal setting

R/W Set a level between 20% and

120% for the rated inverter
current

10AD

h

04269

2000 to

12000

0.01%

B212

Level of electronic
thermal setting, 2nd
motor

R/W

1526h

05414

B013

Electronic thermal
characteristic

R/W Select from two curves,

option codes: *1
00... Reduced torque 1
01... Constant torque
02... Reduced torque 2

10AEh 04270

0, 1, 2

B213

Electronic thermal
characteristic, 2nd
motor

R/W

1527h

05415