“C” Group: Intelligent Terminal Functions

Configur

ing

Dr

iv

e P

a

ra

m

e

ters

3–58

Network Communication Settings

The following table lists parameters that configure the inverter’s serial communications
port. The settings affect how the inverter communicates with a digital operator (such as
SRW–0EX), as well as a ModBus network (for networked inverter applications). The
settings cannot be edited via the network, in order to ensure network reliability. Refer to

“ModBus Network Communications” on page B–1

for more information on controlling

and monitoring your inverter from a network.

“C” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

C071 Communication speed

selection

Three option codes:
04... 4800 bps
05... 9600 bps
06... 19200 bps

✘ ✔

06

04

baud

COM BAU 4800

C072 Node allocation

Set the address of the inverter
on the network. Range is 1 to
32.

✘ ✔

1.

.1

COM ADR 00001

C074 Communication parity

selection

Three option codes:
00... No parity
01... Even parity
02... Odd parity

✘ ✔

00

00

COM PRTY NON

C075 Communication stop bit

selection

Range is 1 to 2

✘ ✔

1

1

COM STP 1BIT

C076 Communication error

select

Selects inverter response to
communications error.
Five options:
00... Trip (error code E60)
01... Decelerate to a stop and
trip (error code E60)
02... Disable
03... Free run stop (coasting)
04... Decelerate to a stop

✘ ✔

02

02

COM ESlct None

C077 Communication error

time-out

Sets the communications
watchdog timer period.
Range is 0.00 to 99.99 sec.

✘ ✔

0.00

0.00

sec.

COM ETIM 000.00s

C078 Communication wait

time

Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms

✘ ✔

0.

0.

msec.

COM Wait 00000ms