Alarm signal, Oper ations and monitor ing, Al0 al2 al1 – Hitachi L2002 User Manual

Page 187

Advertising
background image

L200

2

Inverter

Oper

ations

and Monitor

ing

4–43

Alarm Signal

The inverter alarm signal is active when a fault has
occurred and it is in the Trip Mode (refer to the
diagram at right). When the fault is cleared the
alarm signal becomes inactive.

We must make a distinction between the alarm
signal AL and the alarm relay contacts [AL0],
[AL1] and [AL2]. The signal AL is a logic
function, which you can assign to the open collec-
tor output terminals [11] or [12] or the relay
outputs. The most common (and default) use of the relay is for AL, thus the labeling of
its terminals. Use an open collector output (terminal [11] or [12]) for a low-current logic
signal interface or to energize a small relay (50 mA maximum). Use the relay output to
interface to higher voltage and current devices (10 mA minimum).

Run

Stop

Trip

Fault

Fault

Alarm signal active

STOP

RESET

STOP

RESET

RUN

Option

Code

Terminal

Symbol

Function Name

Output

State

Description

05

AL

Alarm Signal

ON

when an alarm signal has occurred and has not
been cleared

OFF

when no alarm has occurred since the last
clearing of alarm(s)

Valid for outputs:

11, 12, AL0 – AL2

Required settings:

C026, C036

Notes:

By default, the relay is configured as normally
closed (C036=01). Refer to the next page for an
explanation.

In the default relay configuration, an inverter power
loss turns ON the alarm output. the alarm signal
remains ON as long as the external control circuit
has power.

When the relay output is set to normally closed, a
time delay of less than 2 seconds occurs after
powerup before the contact is closed.

Terminals [11] and [12] are open collector outputs,
so the electric specifications of [AL] are different
from the contact output terminals [AL0], [AL1],
[AL2].

This signal output has the delay time (300 ms
nominal) from the fault alarm output.

The relay contact specifications are in

“Control

Logic Signal Specifications” on page 4–6

. The

contact diagrams for different conditions are on the
next page.

RY

+

Example for terminals [AL0], [AL1], [AL2]
(default output configuration shown—
see page

3–54

):

Relay position
shown is for
normal opera-
tion (no alarm).

Example for terminal [11] or [12] (requires
output configuration—see page

3–54

):

AL0

AL2

AL1

Inverter logic
circuit board

Inverter output
terminal circuit

See I/O specs
on page

4–6

.

AL

AL

Load

Power

supply

12 11

CM2

Advertising