B–25, Appendix b – Hitachi L2002 User Manual

Page 261

Advertising
background image

L200

2

Inverter

Appendix B

B–25

The table below lists the holding registers for the “F” Group Main Profile Parameters.

Note 1:

When the value is 10000 (100.0 seconds), a value in the second decimal place
is ignored.

Holding Registers, “F” Group Main Profile Parameters

Func.

Code

Name

R/W

Description

Network Data

Register

Range

Res.

hex

dec.

F002

(high)

Acceleration (1) time
setting *1

R/W Standard default acceleration,

range is 0.01 to 3000 sec.

1014h

04116

1 to

300000

0.01

sec

F002

(low)

R/W

1015h

04117

F202

(high)

Acceleration (1) time
setting, 2nd motor *1

R/W Standard default acceleration,

2nd motor,
range is 0.01 to 3000 sec.

1501h

05377

1 to

300000

0.01

sec

F202

(low)

R/W

1502h

05378

F003

(high)

Deceleration (1) time
setting *1

R/W Standard default deceleration,

range is
0.01 to 3000 sec.

1016h

04118

1 to

300000

0.01

sec

F003

(low)

R/W

1017h

04119

F203

(high)

Deceleration (1) time
setting, 2nd motor *1

R/W Standard default deceleration,

2nd motor,
range is 0.01 to 3000 sec.

1503h

05379

1 to

300000

0.01

sec

F203

(low)

R/W

1504h

05380

F004

Keypad Run key routing R/W Two options; select codes:

00 ...Forward
01 ...Reverse

1018h

04120

0, 1

Advertising