Oper ations and monitor ing, Al0 al2 al1 – Hitachi L2002 User Manual

Page 192

Advertising
background image

Using Intelligent Output Terminals

Oper

ations

and Monitor

ing

4–48

Option

Code

Terminal

Symbol

Function Name

Output

State

Description

07

FBV

Feedback Value
Check

ON

Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is
less than the Feedback Low Limit (C053)

OFF

Transitions to OFF when the PID Feedback
Value (PV) exceeds the PID High Limit
(C052)

Transitions to OFF when the inverter goes
from Run Mode to Stop Mode

Valid for outputs:

11, 12, AL0 – AL2

Required settings:

A076, C052, C053

Notes:

The [FBV] is designed for implementing two-stage
control. The PV high limit and PV low limit param-
eters, C052 and C053, do not function as process
alarm thresholds. Terminal [FBV] does not provide
a PID alarm function.

The example circuit for terminal [12] drives a relay
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from
damaging the inverter’s output transistor.

RY

+

Example (requires output configuration—
see page

3–54

):

Inverter output
terminal circuit

FBV

Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
see pages

4–36

and

3–54

):

AL0

AL2

AL1

Inverter logic
circuit board

See I/O specs
on page

4–6

.

FBV

Load

Power

supply

12 11

CM2