F” group: main profile parameters, F” group: main profile parameters 3–9 – Hitachi L2002 User Manual

Page 89

Advertising
background image

L200

2

Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–9

“F” Group: Main Profile Parameters

The basic frequency (speed) profile is
defined by parameters contained in the
“F” Group as shown to the right. The set
running frequency is in Hz, but accelera-
tion and deceleration are specified in the
time duration of the ramp (from zero to
maximum frequency, or from maximum
frequency to zero). The motor direction
parameter determines whether the keypad
Run key produces a FWD or REV command. This parameter does not affect the intelli-
gent terminal [FWD] and [REV] functions, which you configure separately.

Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the
main profile. Accel and decel values for an alternative profile are specified by using
parameters Ax92 through Ax93. The motor direction selection (F004) determines the
direction of rotation as commanded only from the keypad. This setting applies to any
motor profile (1st or 2nd) in use at a particular time

Output

frequency

t

0

F002

F001

F003

“F” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

F001

Output frequency
setting

Standard default target
frequency that determines
constant motor speed,
range is 0.0 / start frequency
to 400 Hz

✔ ✔

0.0

0.0

Hz

VR 0000.0Hz

F002

Acceleration (1) time
setting

Standard default acceleration,
range is 0.01 to 3000 sec.

✔ ✔

10.0

10.0

sec.

ACC 1 010.00s

F202

Acceleration (1) time
setting, 2nd motor

Standard default acceleration,
2nd motor,
range is 0.01 to 3000 sec.

✔ ✔

10.0

10.0

sec.

2ACC1 010.00s

F003

Deceleration (1) time
setting

Standard default deceleration,
range is 0.01 to 3000 sec.

✔ ✔

10.0

10.0

sec.

DEC 1 010.00s

F203

Deceleration (1) time
setting, 2nd motor

Standard default deceleration,
2nd motor,
range is 0.01 to 3000 sec.

✔ ✔

10.0

10.0

sec.

2DEC1 010.00s

F004

Keypad Run key routing Two options; select codes:

00 .. Forward
01 .. Reverse

✘ ✘

00

00

DIG-RUN FWD

Advertising