Quick start enable – Hitachi L2002 User Manual

Page 178

Advertising
background image

Using Intelligent Input Terminals

Oper

ations

and Monitor

ing

4–34

Quick Start Enable

When the [RDY] input is ON, the inverter is always in Run Mode, even when the motor
rotation has stopped. The pupose of the quick start feature is to improve (decrease) the
startup time of the motor in response to a Run Command.

CAUTION: While the [RDY] input is ON, voltage will be present on the output of the
inverter, even when the motor is still. In this case:
• Do not touch the motor output terminals. Otherwise, there is the danger of electric
shock.
• Do not short the motor leads together or to ground. Otherwise, you may damage the
inverter output circuit

Option

Code

Terminal

Symbol

Function Name

Input

State

Description

52

RDY

Quick Start Enable

ON

Inverter output is always ON (even when motor
rotation has stopped) to improve motor startup
time.

OFF

Inverter output turns OFF normally in Stop
Mode.

Valid for inputs:

C001, C002, C003, C004,
C005

Required settings:

B151=00

Notes:

When the [RDY] input is ON, the inverter output is
energized the Run LED is always ON.

When the [RDY] input is ON, you may edit only
parameters that can be edited in Run Mode. To edit
any parameter, turn OFF the [RDY] input and the
Run Command to put the inverter in Stop Mode.

Function B151 can also enable the Quick Start
function (B151=01). In that case, the [RDY] input
should not be used, because the inverter ignores it.

Example (requires input configuration—see
page

3–47

):

See I/O specs on page

4–6

.

RDY

1

2

3

4

5

L

PCS