B–32, Appendix b – Hitachi L2002 User Manual

Page 268

Advertising
background image

ModBus Data Listing

Appendix B

B–32

A103

[OI]–[L] input active
range start current

R/W The starting point for the

current input range.
Range is 0. to 100.%

1083h

04227

0 to 100

1 %

A104

[OI]–[L] input active
range end current

R/W The ending point for the

current input range.
Range is 0. to 100.%

1084h

04228

0 to 100

1 %

A105

[OI]–[L] input start
frequency enable

R/W Two options:

00... Use A101 start value
01... Use 0Hz

1085h

04229

0, 1

A141

A input select for calcu-
late function

R/W Five options:

00... Digital operator
01... Keypad potentiometer
02... [O] input
03... [OI] input
04... Network variable

108Eh

04238

0 to 4

A142

B input select for calcu-
late function

R/W Five options:

00... Digital operator
01... Keypad potentiometer
02... [O] input
03... [OI] input
04... Network variable

108Fh

04239

0 to 4

A143

Calculation symbol

R/W Calculates a value based on

the A input source (A141
selects) and the B input source
(A142 selects). Three options:
00... ADD (A input + B
input)
01... SUB (A input – B input)
02... MUL (A input x B input)

1090h

04240

0 1, 2

A145

ADD frequency

R/W An offset value that is applied

to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz

1091h

04241

0 to 4000

0.1 Hz

A146

ADD direction select

R/W Two options:

00... Plus (adds A145 value to
the output frequency setting)
01... Minus (subtracts A145
value from the output
frequency setting)

1093h

04243

0, 1

A151

Pot. input active range
start frequency

R/W The output frequency corre-

sponding to the potentiometer
range starting point,
range is 0.0 to 400.0

1095h

4245

0 to 4000

0.1 Hz

Holding Registers for “A” Group Standard Functions

Func.

Code

Name

R/W

Description

Network Data

Register

Range

Res.

hex

dec.