The graph below shows an inverter output profile that starts decelerating to a stop. At
two different points during the deceleration, regenerative voltage elevates the DC bus
level, exceeding the LADSTOP threshold set by B131. When the Over-voltage
LADSTOP feature is enabled by B130 = 01, the inverter stops the deceleration ramp in
each case until the DC bus level is again less than the threshold value.

When using the Over-voltage LADSTOP feature, please note the following:

• When the over-voltage LADSTOP feature is enabled (B130 = 01), the actual

deceleration is sometimes longer than the value set by parameters F003/F203.

• The over-voltage LADSTOP feature does not operate by maintaining a constant

DC bus voltage. So, it is still possible to have an over-voltage trip event during
extreme deceleration.

• If B131 is set lower than the normal DC bus voltage (when not in decel) by mistake, or

if the inverter’s input voltage increases enough, then the inverter will apply LADSTOP
(if enabled) all the time. In this case, the inverter can accelerate and run the motor, but
it cannot decelerate. If you are not sure that B131 > DC bus voltage, measure the DC
bus voltage in your installation and verify that the B131 value is higher.

OVLADSTOP = enable

B130 = 01

Output

frequency

t

t

Over-voltage protection

trip threshold

DC bus level

B131

Over-voltage

LADSTOP threshold

V

Inverter stops

deceleration

Deceleration

resumed

Start

deceleration

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

B130 Over-voltage

LADSTOP enable

Pauses deceleration ramp when
DC bus voltage rises above
threshold level, in order to
avoid over-voltage trip.
Two option codes:
00 .. Disable
01 .. Enable

✘ ✔

00

00

OVLADSTOP OFF