B–30, Appendix b – Hitachi L2002 User Manual

Page 266

Advertising
background image

ModBus Data Listing

Appendix B

B–30

A076

PV source setting

R/W Selects source of Process

Variable (PV), option codes:
00... [OI] terminal (current in)
01... [O] terminal (voltage in)
02... Network
03... Calculate function output

106Dh

04205

0, 1, 2, 3

A077

Reverse PID action

R/W Two option codes:

00... PID input = SP – PV
01... PID input = –(SP – PV)

106Eh

04206

0, 1

A078

PID output limit

R/W Sets the limit of PID output as

percent of full scale,
range is 0.0 to 100.0%

106Fh

04207

0 to 1000

0.1 %

A081

AVR function select

R/W Automatic (output) voltage

regulation, selects from three
type of AVR functions, three
option codes:
00... AVR enabled
01... AVR disabled
02... AVR enabled except
during deceleration

1070h

04208

0, 1, 2

A082

AVR voltage select

R/W 200V class inverter settings:

00... 200
01... 215
02... 220
03... 230
04... 240
400V class inverter settings:
00... 380
01... 400
02... 415
03... 440
04... 460
05... 480

1071h

04209

0 to 5

A092

(high)

Acceleration (2) time
setting

R/W Duration of 2nd segment of

acceleration, range is:
0.01 to 3000 sec.

1074h

04212

1 to

300000

*1

0.1 sec

A092

(low)

R/W

1075h

04213

A292

(high)

Acceleration (2) time
setting, (2nd motor)

R/W Duration of 2nd segment of

acceleration, 2nd motor,
range is: 0.01 to 3000 sec

1518h

05400

1 to

300000

*1

0.1 sec

A292

(low)

R/W

1519h

05401

Holding Registers for “A” Group Standard Functions

Func.

Code

Name

R/W

Description

Network Data

Register

Range

Res.

hex

dec.

Advertising