In most applications a controlled deceleration is desirable, corresponding to B091=00.
However, applications such as HVAC fan control will often use a free-run stop
(B091=01). This practice decreases dynamic stress on system components, prolonging
system life. In this case, you will typically set B088=01 in order to resume from the
current speed after a free-run stop (see diagram below, right). Note that using the default
setting, B088=00, can cause trip events when the inverter attempts to force the load
quickly to zero speed.

NOTE: Other events can cause (or be configured to cause) a free-run stop, such as
power loss (see

“Automatic Restart Mode” on page 3–33

), or an intelligent input

terminal [FRS] signal. If all free-run stop behavior is important to your application (such
as HVAC), be sure to configure each event accordingly.

An additional parameter further configures all instances of a free-run stop. Parameter
B003, Retry Wait Time Before Motor Restart, sets the minimum time the inverter will
free-run. For example, if B003 = 4 seconds (and B091=01) and the cause of the free-run-
stop lasts 10 seconds, the inverter will free-run (coast) for a total of 14 seconds before
driving the motor again.

Stop Mode = free-run stop

B091 = 01

B091 = 01

B088 = 00

B088 = 01

[FW, RV]

Motor

speed

t

Resume from 0Hz

Zero-frequency start

t

Stop Mode = free-run stop

Resume from current speed

[FW, RV]

Motor

speed

Wait time

B003

“B” Function

Run

Mode

Edit

Lo Hi

Defaults

Func.

Code

Name /

SRW Display

Description

–FE(F)

(EU)

–FU

(USA)

Units

B088 Restart mode after FRS

Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00 .. Restart from 0Hz
01 .. Restart from frequency
detected from real speed of
motor (frequency matching)

✘ ✔

00

00

RUN FRS ZST