Using the Front Panel Keypad

In

v

e

rt

er Mounting

and Installation

2–28

If the Potentiometer Enable LED is OFF, follow the steps below.

Select the Keypad for the RUN Command - The RUN
command causes the inverter to accelerate the motor to
the selected speed. The Run command can arrive from
various sources, including the control terminals, the Run
key on the keypad, or the network. In the figure to the
right, notice the Run Key Enable LED, just above the
Run key. If the LED is ON, the Run key is already
selected as the source, and you may skip this step. Note
that the default setting depends on the country.

If the Potentiometer Enable LED is OFF, follow the steps below (the table resumes
action from the end of the previous table).

NOTE: After completing the steps above, the Run Key Enable LED will be ON. This
does not mean the motor is trying to run; it means that the RUN key is now enabled.
DO NOT press the RUN key at this time—complete the parameter setup first.

Action

Display

Func./Parameter

(Starting point)

“A” Group selected

Press the

key.

Speed command source setting

Press the

key again.

00 = Keypad potentiometer
01 = Control terminals
02 = Function F001 setting
03 = ModBus network
10 = Calculate function output

Press the

key.

00 = potentiometer (selected)

Press the

key.

Stores parameter, returns to “A”
Group list

Action

Display

Func./Parameter

(Starting point)

Speed command source setting

Press the

key once.

Run command source setting

Press the

key.

01 = control terminals
02 = Run key on keypad
03 = ModBus network input

Press the

key.

02 = keypad (selected)

Press the

key.

Stores parameter, returns to “A”
Group list

A – – –

FUNC.

A 0 0 1

FUNC.

0 1

2

0 0

STR

A 0 0 1

1

2

5 0.0

RUN

STOP

RESET

FUNC.

STR

HITACHI

POWER

ALARM

RUN

A

Hz

PRG

Run Key Enable LED

A 0 0 1

1

A 0 0 2

FUNC.

0 1

1

0 2

STR

A 0 0 2